NCS-TT105 Smart Temperature Transmitter High Accuracy Version User Manual V3.6

Warning

  1. It is forbidden to disassemble the temperature module by user.
  2. Please check if the supply voltage of temperature transmitter meets the power supply voltage requirements in the manual.

1 Overview

NCS-TT105 smart temperature transmitter adopts fieldbus technology and is a new generation of fieldbus smart temperature transmitter. It is an indispensable field device in process control. The device integrates rich functional modules, which can realize both general detection functions and complex control strategies.

NCS-TT105 adopts digital technology and can be applied to a variety of thermal resistance and thermocouple sensors, with a wide measuring range. The simple interface between the field and the control room greatly reduces the cost of installation, operation and maintenance.

NCS-TT105 smart temperature transmitter supports HART, FF and PA protocols and can be widely used in petroleum, chemical, power plant, metallurgy and other industries.

Figure 1.1 Dimensions of temperature transmitter

Dimensões (unit: mm)

Figure 1.2 The general assembly drawing

General assembly drawing

2 Installation

2.1 Transmitter Installation

Three types of mounting brackets are available:

  • Tube-mounted flat bracket
  • Tube-mounted curved bracket
  • Disk-mounted curved bracket

Corresponding installation methods:

  • Flat bracket tube installation
  • Curved bracket plate installation
  • Curved bracket tube installation

Transmitter Installation

Transmitter Installation

2.2 Hardware Interface

Hardware Interface Description

Sensor wiring instructions (two-channel measurement requires the same settings for both channels):

Sensor Wiring Instructions

Failure Alarm Setting (HART) When faults such as sensor open circuit, short circuit or AD error are detected, the transmitter outputs alarm current.

  • AL dial switch OFF → alarm current > 21.75 mA
  • AL dial switch ON → alarm current < 3.7 mA

Configuration Protection Setting (HART) Dial switch ON = configuration protected Dial switch OFF = configuration allowed

2.3 Bus Power Interface Power and signal share the same pair of cables (bus cable). Do not share conduits with high-power equipment. Shield wires at both ends should be grounded.

3 FF Smart Temperature Transmitter Configuration

3.1 Topological Connection

FF network topology

3.2 Function Block RES, TEMP_SENSORX, DSP, PID, AI, IS, SC, AR, OS

FF bus connection

3.3 Function Configuration Supports Microcyber FF configuration software, NCS4000, NI-FBUS Configurator, DeltaV, etc.

Key operations:

  • Sensor type configuration (SENSOR_TYPE)
  • Two-wire zero point calibration (TWO_WIRES_COMPENSATION)
  • Cold junction compensation (RJ_TYPE)
  • Two-point linearization calibration (CAL_POINT_HI / CAL_POINT_LO)
  • Multi-point linearization calibration (CAL_CURVE_X / CAL_CURVE_Y)
  • User default configuration (USERPARM_SAVE_RST)
  • LCD configuration (DISP_VALUE_X, DISP_SOURCE_X, etc.)