MC0307 Modbus to PA Built-in Module

O MC0307 Modbus to PA built-in module is an embedded conversion module for Modbus-RTU and PROFIBUS PA developed by Microcyber. It is part of the Microcyber M-series built-in core board modules.

The MC0307 operates as a Modbus host and communicates with Modbus-RTU devices through a TTL interface. It converts data from the Modbus device into PA device variable output.

Key Features

  • Modbus-RTU to PROFIBUS PA protocol conversion
  • Built-in core board module design
  • 35 mm × 35 mm module size
  • 2.0 mm pitch, double-row 14-pin connector
  • Modbus host operation
  • TTL interface for Modbus-RTU communication
  • Replaceable Microcyber M-series module design
  • Configuration using the Microcyber configuration tool

Modbus to PROFIBUS PA Conversion

The MC0307 is designed for one-to-one conversion between Modbus and PROFIBUS PA.

As a PA device, the module communicates with the Modbus device through its configured interface. Modbus device data can be mapped to the parameters of the MC0307 transformation block and then provided to the PROFIBUS system through AI, AO, DI and DO function blocks.

The basic data flow is:

Modbus RTU Device → MC0307 → User Transformation Block → AI / AO / DI / DO Function Blocks → PROFIBUS PA System

The MC0307 supports one Modbus slave station. It contains one physical block, one transformation block and 16 function blocks.

Function Blocks

The MC0307 includes:

  • 1 Physical Block
  • 1 User Transformation Block
  • 6 AI function blocks
  • 2 AO function blocks
  • 4 DI function blocks
  • 4 DO function blocks

Each AI function block has 6 channels, each AO function block has 2 channels, each DI function block has 4 channels and each DO function block has 4 channels.

Physical Block

The Physical Block describes hardware information, identification information and diagnostic information specific to the device, including device ID, software version, hardware version and installation date.

User Transformation Block

The User Transformation Block provides Modbus-related parameters, including:

  • 6 analog inputs
  • 2 analog outputs
  • 4 discrete inputs
  • 4 discrete outputs

The transformation block is used to interact with Modbus devices.

Analog Input Block

The AI function block obtains analog process values from the Modbus slave through internal channels and provides the corresponding measured values to the master device through bus communication.

Analog Output Block

The AO function block transfers output data from the master device to the User Transformation Block through the internal channel for the Modbus slave device.

Discrete Input Block

The DI function block obtains input data from the Modbus slave device through internal channels and provides it to the master device through bus communication.

Discrete Output Block

The DO function block transfers discrete output data set by the master device to the User Transformation Block through the internal channel and acts on the Modbus slave device.

MC0307 Modbus to PA Built-in Module

MC0307 Working Modes

The MC0307 can operate in two modes:

  • Configuration Mode
  • Normal Working Mode

The operating mode is selected through the eighth position M of the DIP switch:

ON = Configuration Mode

OFF = Normal Working Mode

Configuration Mode

In Configuration Mode, the MC0307 operates as a Modbus slave station and the Modbus general configuration tool operates as the Modbus master station.

The configuration tool can configure basic device information such as manufacturer ID, device ID and device address source. It can also configure the 16 cyclic parameters and 42 acyclic parameters, including the Modbus function code and register address used to read or write parameters.

After configuration, the configuration information is downloaded to the MC0307 for storage.

Normal Working Mode

In Normal Working Mode, the MC0307 operates as the Modbus master station and the user’s equipment operates as the Modbus slave station.

The MC0307 sends Modbus commands according to the configured working mechanism. Data collected from the Modbus device is mapped to the transformation block parameters by reading and writing Modbus registers.

The transformation block then provides data to the PROFIBUS system through the AI, AO, DI and DO function blocks.

Working Process

The normal working mechanism consists of three stages:

Initialization Stage

The initialization stage is used to test whether Modbus communication is normal.

A Modbus command is selected according to the actual configuration. If a correct response is obtained, the module proceeds to the next stage.

The command selection priority is:

  1. Read serial port address
  2. Read analog input
  3. Read discrete input

At least one of the analog input quantity and discrete input quantity must be non-zero.

Acyclic Stage

The acyclic stage mainly reads the configured data once.

The reading order is:

Analog Input → Discrete Input → Floating Point Data → USIGN32 Data → USIGN16 Data → USIGN8 Data → Octet String Data

When all data has been read correctly, the module enters the cyclic stage. Otherwise, the acyclic stage is executed again until the data has been read successfully.

Cyclic Stage

The cyclic stage performs cyclic reading of cyclic input and output parameters and writing of non-cyclic parameters.

The module sends commands for:

  • Reading analog inputs
  • Writing analog outputs
  • Reading discrete inputs
  • Writing discrete outputs

When an acyclic parameter changes, the corresponding write command is sent.

PA Network Topology

The MC0307 supports PROFIBUS PA network connections.

The manual describes multiple PA network topology methods and specifies that terminal matching resistors should be connected at both ends of the bus to ensure signal quality.

The maximum bus length specified in the manual is 1900 m, and a repeater can extend the length to 10 km.

Modbus Communication Configuration

The Modbus communication parameters are the basic configuration parameters between the MC0307 and the user’s Modbus device.

The module supports configuration of:

  • Baud rate
  • Data bits
  • Parity
  • Interface type
  • Stop bit
  • Slave address
  • CRC check order
  • Timeout
  • Retry count

The available interface types are:

  • TTL
  • RS232
  • RS485

The slave address range is 1–255, the timeout range is 300–1000 ms, and the retry count range is 1–10.

Default Modbus Communication Parameters

Parâmetro Default Value
Slave Address 1
Baud Rate 9600
Data Bits 8
Stop Bit 1
Parity EVEN
CRC Check Low Byte First

Supported Modbus Function Codes

The MC0307 supports the following Modbus function codes:

Código da Função Descrição
01 Read Coil Status
02 Read Discrete Input States
03 Read Holding Register Value
04 Read Input Register Value
05 Write Coil
06 Write Single Register Value
15 Write Multiple Coils
16 Write Multiple Register Values

Cyclic Input and Output Parameters

The User Transformation Block provides:

  • 6 analog input parameters
  • 2 analog output parameters
  • 4 discrete input parameters
  • 4 discrete output parameters

The analog input parameters transfer values and status from the Modbus slave to the AI function blocks. The analog output parameters transfer set values and status from AO function blocks to the Modbus slave.

The discrete input parameters transfer values and status from the Modbus slave to DI function blocks, while the discrete output parameters transfer set values and status from DO function blocks to the Modbus slave.

Acyclic Parameters

In addition to cyclic input and output parameters, the User Transformation Block provides general-purpose acyclic parameters.

These include:

  • 10 floating-point variables
  • 10 32-bit unsigned integer variables
  • 10 16-bit unsigned integer variables
  • 10 8-bit unsigned integer variables
  • 2 32-byte string variables

These parameters can be used to transfer corresponding Modbus data to the PROFIBUS PA side.

Data Format Configuration

MC0307 supports different Modbus data formats for cyclic parameters.

Supported formats include:

  • Float_0123
  • Float_1032
  • Float_3210
  • Float_2301
  • Unsigned8_0
  • Unsigned8_1
  • Unsigned16_01
  • Unsigned16_10
  • Unsigned32_0123
  • Unsigned32_1032
  • Unsigned32_3210
  • Unsigned32_2301
  • Signed8_0
  • Signed8_1
  • Signed16_01
  • Signed16_10
  • Signed32_0123
  • Signed32_1032
  • Signed32_3210
  • Signed32_2301

The suffix in the data type name represents the sequence of data in the Modbus slave registers. The module memory uses little-endian mode.

GSD File Configuration

The Modbus general configuration tool can configure basic information in the GSD file and generate a user-specific device GSD file.

The manual states that the GSD file describes PROFIBUS device features, including supported baud rate, information length, input/output data quantity, diagnostic information and optional module types.

After configuration, the MC0307 can generate a manufacturer GSD file. The manual also describes the use of a profile GSD file and the configuration of the function blocks contained in the manufacturer’s GSD file.

User Product GSD and ID Number

The MC0307 is sold as an OEM module. The user’s PROFIBUS devices have their own intellectual property rights and brand.

According to the manual, a user product should not use the module’s ID number and GSD file name. The user can replace the company name, product model and series number in the GSD file with the information of the user’s own product and form a GSD file for that product.

The ID number configured in the module must match the ID number in the GSD file for the connection.

EDD File

The manual states that PROFIBUS PA uses EDD files and device DTM as device description files.

The MC0307 provides an EDD file template that users can modify according to their own requirements. The manual also notes that changes to the number of parameters may affect EDD parameter reading and that the parameters in the EDD file need to match the configured parameters.

For EDD documentation or device DTM requirements, users can contact Microcyber.

Slave Address Configuration

After module configuration, the MC0307 can be switched back to normal working mode and embedded into the user’s product to form a PROFIBUS PA slave device.

The module supports software-based address configuration through:

  • Bus address setting
  • Serial port address setting

When serial port address setting is disabled, the slave station address can be set through a bus command.

When serial port address setting is enabled, the slave station address is obtained from the Modbus register specified by the bus address register parameter.

Product Development Process

The manual describes the first stage of product development as hardware design.

According to the module dimensions and interface pin definitions, the hardware schematic and PCB of the original user product are redesigned. For M-series compatibility, the interface pin definitions of the M-series modules should be considered during hardware design.

Hardware Interface

The MC0307 uses a 2.0 mm pitch, double-row 14-pin connector. The connector is functionally compatible across the Microcyber M-series embedded core board modules.

The interface includes:

Fixar Nome Descrição
1 SWDIO Data input and output, download interface
2 SWCLK Clock signal, download interface
3 NRST Microcontroller reset signal, download interface
6 RXD UART1 input, TTL level
7 TXD UART1 output, TTL level
13 3.3V_OUT Power output
14 6.2V_OUT Power output
17 WP Write protection enablement
18 RST Reset function
19 S/E Simulation DIP switch
24 IO Modbus communication status indicator
25 IO PA communication status indicator
27 BUS+ Bus power supply positive
28 BUS- Bus power supply negative

Technical Specifications

Parâmetro Especificação
Medindo Objeto Modbus RTU slave unit
PA Bus Power Supply 9–32 VDC
Corrente de Quiescência ≤14 mA
Bus Protocol 2-wire PA protocol
Isolamento Modbus and FF/PA buses are not isolated
Intervalo de Temperatura -40°C a +85°C
Faixa de umidade 5–95% RH
Start-up Time ≤5 s
Tempo de Atualização 0,2 s
Peso 16 g
Coating Polyester epoxy resin

Compatibilidade Eletromagnética

The manual specifies electromagnetic compatibility requirements including:

GB/T 18268.1-2010

e

GB/T 18268.23-2010

as stated in the technical specification section.

Maintenance

The MC0307 provides a PA communication status indicator.

When the indicator is abnormal, the manual identifies possible causes including:

  • No PA communication
  • Power failure
  • Internal failure

The recommended checks include checking the PA host equipment, interface equipment, power supply and connection. For an internal failure, the manual advises contacting technical support.

Perguntas Frequentes

What is the MC0307 Modbus to PA built-in module?

MC0307 is a built-in conversion module for Modbus-RTU and PA protocol. It operates as a Modbus host, communicates with the Modbus device through a TTL interface and converts device data into PA device variable output.

How many Modbus slave devices does MC0307 support?

The MC0307 supports one Modbus slave station.

What function blocks are included in MC0307?

The module includes 1 Physical Block, 1 User Transformation Block, 6 AI function blocks, 2 AO function blocks, 4 DI function blocks and 4 DO function blocks.

What Modbus function codes are supported?

MC0307 supports function codes 01, 02, 03, 04, 05, 06, 15 and 16.

What is the PA bus power supply range?

The specified PA bus power supply is 9–32 VDC.

What is the operating temperature range?

The specified temperature range is -40°C a +85°C.

Does MC0307 support GSD files?

Yes. The Modbus general configuration tool can configure basic GSD information and generate a user-specific device GSD file.

Does MC0307 provide an EDD file?

The manual states that the module provides an EDD file template, which users can modify according to their requirements.

MC0307 User Manual

For detailed information about module configuration, Modbus communication, function blocks, GSD files, EDD files, installation, maintenance and technical specifications, refer to the MC0307 Modbus to PA Built-in Core Module User Manual.

Download the MC0307 User Manual