Transmisor HART de Doble Canal NCS-TT305H

NCS TT305

Descripción general del producto

The NCS-TT305 series HART temperature transmitter is a TÜV-certified high-precision, low-temperature-drift, and high-reliability product, serving as an important field device in process control. This device integrates a rich set of functional modules, enabling both general detection functions and complex control strategies.

The NCS-TT305 series temperature transmitter supports 4–20 mA + HART protocol y LCD display, and can be widely used in industries such as petroleum, chemical, power, and metallurgy.

Señal de salida 4–20mA + HART, Burst Mode Supported
Versión del protocolo HART 7
Voltaje de alimentación Non-Ex: (13~45)VDC; Ex d: (13~45)VDC; Ex ia: (13~30)VDC
Cableado del sensor conexión de 2 hilos, 3 hilos o 4 hilos
Tipos de Señal de Entrada Resistance (Ω): 0~500Ω, 0~2000Ω, 0~4000Ω, 0~40000Ω;
RTD: Cu50, Cu50_GOST, Cu100, Cu100_GOST, Pt50_GOST, Callendar-Van Dusen (Pt100), Pt100, Pt100_GOST, Pt200, Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000;
Voltage (mV): -100mV~100mV;
Thermocouple (TC): B, E, J, K, N, R, S, T, L_GOST, A (W5ReW20Re), C (W5ReW26Re), D (W3ReW25Re), NiCrAuFe, CuAuFe
Número de canales Doble canal
Precisión actual Current accuracy: 0.05%; Current temperature drift: 0.005%/°C
Aislamiento eléctrico 2kVAC (test) / 50VAC (working)
Efecto del voltaje ±0,0051 TP3T/V
Tiempo de respuesta 1.0~1.65s, depending on sensor type and wiring
Tiempo de arranque Menos de 10 segundos
Constante de tiempo de amortiguación 0~32s
EMC IEC 61326
Protección contra explosiones IECEx: Ex ia IIC T6…T4 Ga;
ATEX: II2G Ex db IIC T6…T4 Gb, II2D Ex tb IIIC T85°C…T110°C Db
Pantalla LCD Compatible
Operación del teclado Supported (local button configuration)
Temperatura de funcionamiento -40~85°C; optional -55~85°C
Rango de humedad 5~95%RH
Temperatura de almacenamiento -50~85°C
Señales de Alarma Saturation Low: [3.75–4.0)mA, default 3.8mA;
Saturation High: (20–20.8]mA, default 20.5mA;
Alarm Low: [3.5–3.7]mA, default 3.6mA;
Alarm High: [21.0–23.0]mA, default 21.75mA
Vibration Specification 2–25Hz: ±1.6mm; 25–100Hz: ±4g
Dimensiones 139.7 × 111.9 × 112.0mm
Materiales de construcción Aluminum, Polycarbonate
Peso Approx. 1.67kg
  • Converts RTD, thermocouple, linear resistance, and millivolt (mV) input signals into a 4–20 mA output with HART 7 communication. Burst mode is supported.
  • Dual-channel sensor input supports sensor hot backup and cross-channel temperature drift monitoring between Sensor 1 and Sensor 2.
  • Hot backup automatically switches the loop output to the healthy sensor when the active channel fails due to an open or short circuit, ensuring uninterrupted process measurement without manual intervention.
  • Supports corrosion detection for 4-wire RTDs and 2-wire thermocouples by monitoring wiring resistance against configurable thresholds (RTD: 5–250 Ω, default 50 Ω; thermocouple: 5–10,000 Ω, default 5,000 Ω).
  • Supports multi-point linearization to improve measurement accuracy beyond standard factory calibration.
  • Advanced device diagnostics comply with the NE107 four-status model (Failure, Function Check, Out of Specification, and Maintenance Required), with independent alarm-level settings for Standard and SIL operating modes.
  • Integrated LCD display and push-button interface enable complete local configuration and diagnostics without requiring a HART modem.
  • Assessed in accordance with IEC 61508-2/-3 and IEC 61511 field-data requirements. Supports SIL 2 safety functions in single-channel (HFT = 0) architecture and SIL 3 in redundant (HFT = 1) architecture.
  • Available with intrinsically safe and flameproof explosion protection, including IECEx Ex ia IIC T6…T4 Ga and ATEX II2G Ex db IIC T6…T4 Gb / II2D Ex tb IIIC T85°C…T110°C Db certifications.
Aún no hay archivos actualizados.