Who is this for?
If you are a control system engineer, plant operator, system integrator, or maintenance manager working with FOUNDATION Fieldbus (FF) or PROFIBUS PA networks, and you need to interface fieldbus systems with conventional analog control valves, actuators, or other 4-20mA devices, the NCS-FI105 is built for you.
What problem does it solve?
Modern fieldbus systems (FF and PA) offer powerful digital communication, but many final control elements – such as control valves, positioners, and actuators – still accept only conventional 4-20mA analog signals. This creates a compatibility gap that forces engineers to choose between advanced fieldbus control and legacy analog devices.
The NCS-FI105 eliminates this gap. It is a fieldbus to current converter that receives digital fieldbus signals from FF or PA networks and converts them into 4-channel 4-20mA analog output signals. This allows your fieldbus control system to seamlessly operate analog actuators, control valves, and other current-driven devices without costly replacements or complex interface hardware.
Why Microcyber?
Microcyber Corporation is a national high-tech enterprise founded by the Shenyang Institute of Automation, Chinese Academy of Sciences. We developed China’s first internationally certified fieldbus protocol master stack, the first domestically certified fieldbus instrument, and the first TÜV Germany-certified safety instrument. We co-established the first domestic industrial Ethernet protocol standard EPA and the first industrial wireless communication protocol standard WIA-PA, both recognized as IEC international standards. Our products and technologies have earned two National Science and Technology Progress Awards, one National Science and Technology Invention Award, and we have successfully completed more than 200 large-scale automation projects worldwide. We are ISO 9001:2008 and ISO/TS16949 certified – when you choose NCS-FI105, you are choosing field-proven, mission-critical technology.
Key Features – What Matters to Engineers and Procurement
| Priority | How NCS-FI105 Delivers |
|---|---|
| Compatibilidad con protocolos | Compatible con FOUNDATION Fieldbus (FF) H1 y PROFIBUS PA – one converter for both major fieldbus systems. |
| Multi-Channel Output | Proporciona 4 independent 4-20mA analog output channels – control up to four analog devices from a single fieldbus node. |
| Alta precisión | < 0.05% accuracy – ensures precise analog signal conversion for critical control loops. |
| Flexible Output Loading | Supports load resistance up to 1350Ω – compatible with a wide range of analog actuators and control valves. |
| Rich Function Blocks | FF version includes Resource Block, Transducer Block, Analog Output Block, PID Block, Ratio Block, and Lead Lag Block – enabling advanced control strategies directly in the field. |
| On-Site Adjustment | Magnetic bar operation (Zero/Span holes) and optional LCD display allow full local configuration – channel selection, range setting, bus address, and decimal point adjustment without a communicator. |
| Fieldbus-Ready | Complies with FF Specification and PROFIBUS PA Profile 3.01. Supports both cyclical y non-cyclical data communication. |
| Rugged Design | IP65 protection, wide operating temperature range (-40°C to 85°C), and EMC compliant to IEC 61000 – suitable for harsh industrial environments. |
Product Overview – FF and PA Versions
The NCS-FI105 Series is available in two protocol variants:
| Modelo | Protocolo | Target Applications |
|---|---|---|
| NCS-FI105F | FOUNDATION Fieldbus (FF) H1 | FF-based control systems, advanced process control, DeltaV, NI-FBUS |
| NCS-FI105P | PROFIBUS PA | PA-based systems, Siemens PDM/Step7, European-origin DCS/PLC |
Both versions share the same hardware platform, 4-channel 4-20mA output, and magnetic bar on-site adjustment – only the communication protocol differs.
Function Blocks
NCS-FI105F (FF Version)
| Function Block | Descripción |
|---|---|
| Resource Block | Contains hardware-associated resource data. |
| Transducer Block | Converts I/O device variables into engineering data. |
| Display Transducer Block | Configures process variables displayed on LCD. |
| Analog Output Block | Transmits output data to transducer block and applies to physical devices. |
| PID Block | Provides setpoint treatment, PV filtering, feed-forward, output tracking, and alarm functions. |
| Ratio Block | Realizes ratio control between two input data. |
| Lead Lag Block | Provides dynamic compensation for feed-forward control. |
NCS-FI105P (PA Version)
| Function Block | Descripción |
|---|---|
| Physical Block | Describes device hardware, identification, and diagnostic information. |
| Transducer Block | Isolates function block from I/O characteristics; handles calibration and linearization. |
| Analog Output Block | Transmits output data to transducer block and applies to physical devices. |
Especificaciones técnicas
Basic Parameters
| Parámetro | Especificaciones |
|---|---|
| Señal de entrada | Fieldbus (FF H1 / PROFIBUS PA) |
| Señal de salida | 4-20mA analog (4 channels) |
| Tipo de salida | NPN collector output |
| Fuente de alimentación | 9-32 CC |
| Current Dissipation (Static) | ≤ 14 mA |
| Fieldbus Baud Rate | 31.25 kbit/s, current-mode |
| Insulation | Between housing and terminal board: 500 Vrms (707 VDC) |
| Pantalla | Optional: 6-digit numeric + 5-character LCD |
| Temperatura de funcionamiento | -40°C to 85°C (no display) / -30°C to 70°C (with display) |
| Rango de humedad | 0% – 100% RH |
| Tiempo de arranque | ≤ 5 segundos |
| Clase de protección | IP65 |
| EMC Compliance | Designed to comply with IEC 61000 |
Technical Performance
| Parámetro | Especificaciones |
|---|---|
| Precisión | < 0.05% |
| Carga máxima | 1350Ω |
| Load Power | 9-32 VDC (Note: supply voltage ≥ output current × load resistance + 5VDC) |
| Temperature Effect | < ±50 ppm/°C |
Physical Properties
| Parámetro | Especificaciones |
|---|---|
| Conexión eléctrica | 1/2-14 NPT |
| Material of Construction | Aluminum |
| Peso | 1,1 kg |
Configuration & Software Support
For FF Version (NCS-FI105F):
| Herramienta | Descripción |
|---|---|
| Microcyber Configurator | Full configuration and diagnostics |
| NCS4000 DCS | Integrated with Microcyber DCS |
| NI-FBUS Configurator | National Instruments FF configuration |
| Emerson DeltaV | Direct integration with DeltaV system |
| FF Configurator | Standard FF configuration software |
Configuration Capabilities:
-
Two-point calibration (CAL_POINT_HI / CAL_POINT_LO)
-
Multi-point calibration (up to 8 points via CAL_CURVE_X / CAL_CURVE_Y)
-
LCD display content configuration (BLOCK_TAG_X, RELATIVE_INDEX_X, SUB_INDEX, MNEMONIC_X, DECI_PNT_NUMB_X, ACTIVE_X)
For PA Version (NCS-FI105P):
| Herramienta | Descripción |
|---|---|
| Siemens Simatic PDM | Full device management and configuration |
| Siemens Step7 | Hardware configuration and cyclic data setup |
Configuration Capabilities:
-
Two-point linearization calibration (via Calibration menu)
-
Bus address setting (0-126)
-
Measurement value display source selection
-
Decimal point position setting
-
Linearization type selection (factory / user)
Cyclical Data Communication: Supports PROFIBUS DP cyclical data exchange via DP/PA coupler or linker. GSD file provided for easy integration with Siemens Step7.
Non-Cyclical Data Communication: Supports PROFIBUS DP non-cyclical data exchange via Class 2 master (e.g., CP5611) using SIMATIC PDM.
On-Site Adjustment – Magnetic Bar Operation
The NCS-FI105 features magnetic bar operation through two jacks marked “SPAN” and “ZERO” on top of the electronic housing. Four virtual keys are simulated:
-
[M] Mode Key – Switch between operable modes
-
[↑] Input Adjustment Key – Increment values
-
[↓] Input Adjustment Key – Decrement values
-
[Enter] Confirmation Key – Execute confirmation
Supported Adjustment Functions – NCS-FI105F (FF Version):
| Mode | Función | Descripción |
|---|---|---|
| 02 | Channel Selection | Set channel number (CH_1 to CH_4) |
| 16 | Lower Range Limit | Adjust characteristic curve lower limit |
| 17 | Upper Range Limit | Adjust characteristic curve upper limit |
Supported Adjustment Functions – NCS-FI105P (PA Version):
| Mode | Función | Descripción |
|---|---|---|
| 02 | Channel Selection | Set display channel (CH_1 to CH_4 or LOOP) |
| 11 | Display Source | Select FINAL_VALUE, RETURN_VALUE, or AO_SETPOINT |
| 13 | Bus Address | Set PROFIBUS user address (0-126) |
| 14 | Decimal Point | Set decimal point position (up to 5 decimals) |
| 22 | Linearization Type | Select factory calibration or user calibration |
General Operation:
-
In measurement value display mode, press [M] to switch modes.
-
When desired mode is displayed, remove both magnetic sticks.
-
Press [↑] or [↓] to adjust value.
-
Press [Enter] to confirm.
-
Press [M] to return to measurement display.
Restore Factory Defaults:
-
Turn off power.
-
Insert both magnetic bars into Zero and Span holes simultaneously.
-
Turn on power – LCD displays “RST?”.
-
Remove both bars, then re-insert both bars until progress bar reaches 100%.
-
Remove both bars – LCD displays “R_OK” when successful.
Nota: If no key operation occurs within 1 minute (no magnetic sticks inserted), the device automatically returns to normal display mode.
Jumper Configuration
NCS-FI105F (FF Version) and NCS-FI105P (PA Version)
| Jumper | Función | Descripción |
|---|---|---|
| SIM | Simulation Jumper | Enables simulation mode for testing |
| WP | Write Protection Jumper | Prevents configuration changes when enabled |
| RST | Factory Reset Jumper | Restores all configuration to factory defaults |
Important Notes:
-
When using RST jumper to restore factory defaults, power off the transmitter, remove the RST jumper, then power on again. If the RST jumper remains in place, configuration data will revert to factory defaults every time the device restarts.
-
WP jumper (write protection) prevents any accidental or unauthorized changes to device configuration – ideal for critical installations.
Typical Applications
-
Control Valve Interface – Convert fieldbus signals to 4-20mA for controlling pneumatic or electric control valves
-
Actuator Control – Interface fieldbus DCS/PLC with analog actuators in process plants
-
Legacy Analog Device Integration – Connect modern fieldbus systems to existing analog instruments without replacing hardware
-
Multi-Device Control – One fieldbus node controls up to four analog devices simultaneously
-
Retrofit Projects – Upgrade plant control systems to fieldbus while preserving existing analog final control elements
Installation & Wiring
Mounting Options:
-
Pipe mounting flat bracket (vertical pipe, Φ50mm)
-
Plate mounting angle bracket (panel/dashboard)
-
Pipe mounting angle bracket (horizontal pipe, Φ50mm)
Cableado
-
Power and signal share a single pair of cables (bus cable).
-
Use IEC 61158-2 recommended fieldbus cables for FF/PA.
-
Terminal board located on rear cover side.
-
Signal wires should be single-point grounded.
-
Bus cable shield should be floating on converter side, grounded on bus power side.
-
Bus cable should not share conduits or trunks with other equipment power lines.
Terminal Board Pinout:
-
Terminal board connects fieldbus, current output signal, D/A board, and communication board.
Ordering Information
| Modelo | Protocolo | Canales | Salida | Potencia |
|---|---|---|---|---|
| NCS-FI105F | FOUNDATION Fieldbus H1 | 4 | 4-20 mA | 9-32 CC |
| NCS-FI105P | PROFIBUS PA | 4 | 4-20 mA | 9-32 CC |
Options:
-
LCD Display – Optional 6-digit numeric + 5-character LCD with backlight
-
Display Configuration – Customizable via function block parameters
Accessories:
-
Mounting brackets (pipe flat / plate angle / pipe angle)
-
U-bolts for pipe mounting