Product Overview

NCS-TT306HR1 Smart Temperature Transmitter is a single-channel rail-mounted temperature transmitter featuring high reliability, excellent long-term stability, high measurement accuracy, and low temperature drift. Equipped with advanced diagnostic functions, it meets the measurement requirements of critical process stages and serves as an indispensable field temperature measurement device in process control. It supports measurements from various types of resistance temperature detectors (RTDs), thermocouples (TCs), resistors (Ω), and voltage (mV) sensors, and is compatible with the 4-20mA + HART communication protocol. The product has obtained multiple international certifications, including explosion-proof, CE-EMC, SIL, PAC, EAC, and FCG, and is widely used in process industries such as petroleum, chemical, power generation, and metallurgy.

Output Signal 4~20mA + HART, Burst mode supported
Protocol Version HART 7
Supply Voltage Non-IS: (10~45)VDC / (13~45)VDC (without LCD/with LCD); IS: (10~30)VDC / (13~30)VDC (without LCD/with LCD)
Sensor Wiring 2-wire, 3-wire, or 4-wire connection
Input Signal Types Resistance (Ω): 0~500Ω, 0~2000Ω, 0~4000Ω, 0~20000Ω, 0~40000Ω; RTD: Cu50, Cu50_GOST, Cu100, Cu100_GOST, Pt50_GOST, Callendar_Van_Dusen(Pt100), Pt100, Pt100_GOST, Pt200, Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000; Voltage (mV): -100mV~100mV; Thermocouple (TC): B, E, J, K, N, R, S, T, L_GOST, A(W5ReW20Re), C(W5ReW26Re), D(W3ReW25Re), NiCrAuFe, CuAuFe
Channel Count Single channel
Accuracy Class Refer to user manual
Current Accuracy Current accuracy: 0.03%; Current temp drift: 0.005%/℃
Electrical Isolation (Test/Working) 2KVAC/50VAC
Voltage Effect ±0.005%/V
Response Time 1.0~1.65s depending on sensor type and wiring
Startup Time ≤10s
Damping Time Constant (0~32)s
EMC IEC 61326 (GB/T 18268)
Explosion Protection Ex ia IIC T4/T6 Ga
LCD Display Supported
Keypad Operation Supported
Operating Temperature (-40~85)℃; (-55~85)℃ (optional)
Humidity Range (5~95)%RH
Storage Temperature (-50~85)℃
Alarm Signals Saturation Low: [3.75-4.0)mA, default 3.8mA; Saturation High: (20-20.8]mA, default 20.5mA; Alarm Low: [3.5-3.7]mA, default 3.6mA; Alarm High: [21.0-23.0]mA, default 21.75mA
Vibration Spec 2-25Hz: ±1.6mm; 25-100Hz: ±4g
Protection Rating IP20
Weight Approx. 130g
  • Converts various input signals into 4–20 mA output signals and HART communication signals.
  • Supports measurement of various RTDs, thermocouples, resistance, and voltage signals.
  • Single-channel input with support for 2-wire, 3-wire, and 4-wire RTD connections.
  • High measurement accuracy with Pt100 accuracy up to ±0.1°C, low temperature drift of ±0.003°C/°C, and analog output accuracy of 0.03% FS.
  • Supports transmitter-sensor matching to improve measurement accuracy.
  • Supports sensor and hardware fault diagnostics in compliance with NE107 recommendations.
  • Designed to meet intrinsically safe explosion-proof requirements for hazardous area applications.
  • Fully assessed in accordance with IEC 61508 and certified for SIL 2/3 functional safety applications.
  • FCG certified.
  • Provides EDD, FDI, and DTM files for compatibility with various DCS systems.