1. Home
  2. /
  3. Product
  4. /
  5. Smart Temperature Transmitters
  6. /
  7. DIN Rail Mounted Temperature...
  8. /
  9. NCS-TT106F-R1 Rail-Mounted Single-Channel FF...

NCS-TT106F-R1 Rail-Mounted Single-Channel FF Temperature Transmitter

NCS-TT106F-R1

Product Overview

NCS-TT106F-R1 Smart Temperature Transmitter is a single-channel rail-mounted temperature transmitter featuring high reliability, excellent long-term stability, high measurement accuracy, and low temperature drift. Equipped with advanced diagnostic functions, it meets the measurement requirements of critical process stages and serves as an indispensable field temperature measurement device in process control. It supports measurements from various types of resistance temperature detectors (RTDs), thermocouples (TCs), resistors (Ω), and voltage (mV) sensors, and is compatible with the FF communication protocol. The product has obtained multiple international certifications, including explosion-proof, CE-EMC, PAC, EAC, and FCG, and is widely used in process industries such as petroleum, chemical, power generation, and metallurgy.

Output Signal FOUNDATION Fieldbus H1
Protocol Version ITK 6
Supply Voltage Non-IS: (9~32)VDC, Quiescent Current ≤14mA;
IS: (9~17.5)VDC, Quiescent Current ≤14mA
Sensor Wiring 2-Wire, 3-Wire, or 4-Wire Connection
Input Signal Types Resistance (Ω): 0-500Ω, 0-4000Ω;

RTD: Cu50, Cu100, Pt100, Pt1000, Custom Defined RTD;

Voltage (mV): -100mV~100mV;

Thermocouple (TC): B, E, J, K, N, R, S, T, Custom Defined TC

Channel Count Single Channel
Accuracy Class Refer to User Manual
Electrical Isolation 1KVAC
Voltage Effect ±0.005%/V
Response Time 0.5s
Startup Time ≤5s
Damping Time Constant (0~32)s
EMC IEC 61326 (GB/T 18268)
Explosion Protection Ex ia IIC T4 Ga
LCD Display Not Supported
Keypad Operation Not Supported
Operating Temperature (-40~85)℃
Humidity Range (5~95)%RH
Storage Temperature (-50~85)℃
Vibration Spec 2-25Hz: ±1.6mm;
25-100Hz: ±4g
Protection Rating IP20
Weight Approx. 100g
  • Implements standardized communication in accordance with the FOUNDATION Fieldbus H1 standard.
  • Supports measurement of various RTDs, thermocouples, resistance, and voltage signals.
  • Single-channel input with support for 2-wire, 3-wire, and 4-wire RTD connections.
  • High measurement accuracy with Pt100 accuracy up to ±0.1°C and low temperature drift of ±0.003°C/°C.
  • Supports external Pt100 cold-junction compensation with accuracy up to ±0.15°C.
  • Supports open-circuit and short-circuit detection to help identify sensor faults.
  • Complies with FISCO intrinsically safe explosion-proof requirements for hazardous area applications.
  • Supports standard DIN-TH35 rail mounting for convenient installation.
  • FCG certified.
  • Provides EDD files for compatibility with various DCS systems.

Inquiry information