NCS-TT106P-R1 Rail Mounted PA Single Channel Temperature Transmitter

NCS-TT106P-R1

Product Overview

The NCS-TT106P-R1 Smart Temperature Transmitter is a single-channel, DIN-rail mounted temperature transmitter featuring high reliability, high long-term stability, high measurement accuracy, and low temperature drift. Equipped with advanced diagnostic functions, it meets the measurement requirements of critical process sections and is an indispensable field temperature measurement device in process control. It is suitable for various sensors including resistance temperature detectors (RTD), thermocouples (TC), resistors (Ω), and voltage (mV) sensors, and supports the PROFIBUS PA protocol. The product has obtained multiple certifications including explosion protection, CE-EMC, PAC, and EAC, and is widely used in process industries such as oil, chemical, power, and metallurgy.

Output Signal PROFIBUS PA
Protocol Version Profile 3.02
Supply Voltage Non-Ex: (9~32)VDC, quiescent current ≤14mA;
Ex: (9~17.5)VDC, quiescent current ≤14mA
Sensor Wiring 2-wire, 3-wire, or 4-wire connection
Input Signal Types Resistance (Ω): 0-500Ω, 0-4000Ω;
RTD: Cu50, Cu100, Pt100, Pt1000, Custom defined RTD;
Voltage (mV): -100mV~100mV;
Thermocouple (TC): B, E, J, K, N, R, S, T, Custom defined TC
Number of Channel Single channel
Accuracy Class Refer to user manual
Electrical Isolation 1KVAC
Voltage Effect ±0.005%/V
Response Time 0.5s
Startup Time ≤5s
Damping Time Constant (0~32)s
EMC IEC 61326 (GB/T 18268)
Explosion Protection Ex ia IIC T4 Ga
LCD Display Not supported
Button Operation Not supported
Operating Temperature (-40~85)℃
Humidity Range (5~95)%RH
Storage Temperature (-50~85)℃
Vibration Spec 2-25Hz: ±1.6mm; 25-100Hz: ±4g
Protection Level IP20
Weight Approx. 100g
  • Standardized communication compliant with PROFIBUS PA Profile 3.02
  • Supports a wide range of RTDs, thermocouples, and resistance/voltage signal measurements
  • Single-channel input, with RTD support for 2-wire, 3-wire, and 4-wire connections
  • High accuracy (Pt100: ±0.1°C) and low temperature drift (Pt100: ±0.003°C/°C)
  • External Pt100 cold junction compensation with accuracy of ±0.15°C
  • Open/short circuit detection helps diagnose sensor faults
  • Compliant with FISCO intrinsic safety explosion protection requirements, ensuring safe operation in hazardous areas
  • Standard DIN-TH35 rail mounting
  • PI-certified
  • GSD/EDD files provided for compatibility with multiple DCS systems

Inquiry information