The M0310, as one of the Microcyber M-series OEM embedded modules, enables the conversion from Modbus RTU to HART. With its core advantages of consistent size, interface, easy upgrades, and simple configuration, this series of modules is widely compatible with various products such as transmitters, intelligent measuring devices, and instruments, making it an ideal choice for users to quickly develop HART devices.

Output Signal 4~20mA + HART
Protocol Version HART 7
Supply Voltage (11.9~35)VDC
Measuring Object Modbus RTU Slave Device
Modbus RTU Slave Number 1
Modbus RTU Slave Address Range 1–247
Modbus RTU Supported Baud Rates 1200, 2400, 4800, 9600, 19200, 35700, 38400, 57600 bps
Modbus RTU Supported Commands 1, 2, 3, 4, 5, 6, 16
Input Signal Physical Interface TTL Interface
Isolation Voltage 1KVAC
Current Output Accuracy Current Accuracy: 0.03%;
Current Temp Drift: 0.005%/℃
Load Resistance 0–1500Ω (Normal);
230–1100Ω (HART Communication)
Startup Time ≤5s
Update Time 0.25s, 0.5s, 0.75s, 1s, 1.25s, 1.5s, 1.75s, 2s (Configurable)
Damping Time Constant (0~32)s
EMC IEC 61326 (GB/T 18268)
Operating Temperature (-40~85)℃
Humidity Range (5~95)%RH
Storage Temperature (-50~85)℃
Electrical Interface 2.54mm Pitch 16-Pin Standard Socket
Dimensions (65×42×15)mm
Weight Approx. 16g
  • Rapid time-to-market: Users do not need HART development knowledge or a dedicated HART development system to quickly develop HART products with independent intellectual property rights.
  • Same size: M-series embedded modules all share the same dimensions of 65 mm (L) × 42 mm (W).
  • Same interface: M-series embedded modules use a 2.54 mm pitch 2×8 dual-row header, ensuring functional compatibility.
  • Easy upgrades: Different M-series embedded modules can be replaced to implement devices with different communication protocols.
  • Flexible configuration: With the dedicated HARTMPT configuration tool, users can freely and flexibly configure various module parameters according to application requirements.
  • Easy to use: The module reads and writes parameter data of the user’s product through a serial interface and automatically converts it into HART device variables and dynamic variable parameters for communication with the HART master station.
  • Wide applications: Widely used in transmitters, intelligent measurement devices, and industrial instruments.
  • OEM available: Users retain independent intellectual property rights, as well as brand and trademark registration rights. Customized DD, FDI, and DTM services are also available.
  • HART pre-certification: Pre-certified for protocol consistency by FieldComm Group (FCG), helping accelerate formal HART certification and reduce development time.