NCS-TT105P Field-Mounted Dual-Channel PA Temperature Transmitter

NCS-TT105P

Product Overview

NCS-TT105P Smart Temperature Transmitter is a dual-channel, field-mounted temperature transmitter featuring an LCD display and button-based parameter configuration. It offers high reliability, long-term stability, measurement accuracy, and low temperature drift. Equipped with advanced diagnostics and sensor redundancy with hot-swap capabilities, it meets the measurement requirements of critical process stages, making it an indispensable field temperature measurement device for process control. It is suitable for measuring various types of resistance temperature detectors (RTD), thermocouples (TC), resistors (Ω), and voltage (mV) sensors, and supports PA communication protocol. The product has obtained multiple international certifications, including Intrinsic Safety, Flameproof, PAC, EAC, and PI, and is widely used in process industries such as petroleum, chemicals, power, and metallurgy.

Output Signal PROFIBUS PA
Protocol Version Profile 3.02
Supply Voltage Non-IS: (9~32)VDC, Quiescent Current ≤14mA;
IS: (9~17.5)VDC, Quiescent Current ≤14mA;
Flameproof: (9~32)VDC, Quiescent Current ≤14mA
Sensor Wiring 2-Wire, 3-Wire, or 4-Wire Connection
Input Signal Types Resistance (Ω): 0-500Ω, 0-4000Ω;

RTD: Cu50, Cu100, Pt100, Pt200, Pt500, Pt1000;

Voltage (mV): -100mV~100mV;

Thermocouple (TC): B, E, J, K, N, R, S, T

Channel Count Dual Channel
Accuracy Class Refer to User Manual
Electrical Isolation 1KVAC
Voltage Effect ±0.005%/V
Response Time 0.8~1.3s Depending on Sensor Type and Wiring
Startup Time ≤8s
Damping Time Constant (0~32)s
EMC IEC 61326 (GB/T 18268)
Explosion Protection Ex db IIC T5/T6 Gb / Ex ia [ia Ga] IIC T4/T6 Ga
LCD Display Supported
Keypad Operation Supported
Operating Temperature (-40~85)℃
Humidity Range (5~95)%RH
Storage Temperature (-50~85)℃
Vibration Spec 2-25Hz: ±1.6mm;
25-100Hz: ±4g
Protection Rating IP67
Weight 1.0kg
  • Implements standardized communication in accordance with PROFIBUS PA Profile 3.02.
  • Supports measurement of various resistance temperature detectors (RTDs), thermocouples, resistance, and voltage signals.
  • Dual-channel input with a 6-terminal sensor design that supports flexible dual-input combinations.
  • High measurement accuracy with Pt100 accuracy up to ±0.1°C and low temperature drift of ±0.003°C/°C.
  • Supports open-circuit and short-circuit detection to help identify sensor faults.
  • Complies with intrinsically safe and flameproof explosion-protection requirements for safe operation in hazardous areas.
  • PI certified.
  • Provides GSD and EDD device description files compatible with various DCS systems.

Inquiry information