| Rated Voltage |
(9~35)VDC |
| Interface |
PROFIBUS PA, FOUNDATION Fieldbus H1 |
| Rated Current |
≤1A |
| No-Load Current |
MCAFD4: <10mA
MCAFD8: <15mA
MCAFD12: <20mA |
| Power Consumption |
MCAFD4: <180mW
MCAFD8: <250mW
MCAFD12: <350mW |
| Trunk Voltage Drop |
<0.3VDC |
| Trunk-to-Segment Voltage Drop |
<1VDC |
| Max Segment Output Voltage |
≤32VDC |
| Max Segment Output Current |
(60±0.5)mA |
| Short-Circuit Protection Current |
<800μA |
| Trunk Connector Qty |
2 |
| Trunk Connector |
M16 × 1.5 Increased-Safety Explosion-Proof Gland |
| Trunk Cable Diameter |
(4~9)mm |
| Trunk Conductor Cross-Section |
(0.2~2.5)mm² |
| Trunk Terminal Type |
Spring Clamp Terminal |
| Segment Connector Qty |
MCAFD4: 4
MCAFD8: 8
MCAFD12: 12 |
| Segment Connector |
M16 × 1.5 Increased-Safety Explosion-Proof Gland |
| Segment Cable Diameter |
(4~9)mm |
| Segment Conductor Cross-Section |
(0.2~2.5)mm² |
| Segment Terminal Type |
Spring Clamp Terminal |
| Termination Setting |
Automatic, No Manual Setting Required |
| Temperature Range |
(-20~70)℃ |
| Humidity Range |
(5~95)%RH |
| Storage Temperature |
(-50~85)℃ |
| Protection Level |
IP67 |
| Explosion Protection |
Ex ec [ic] IIC T4 Gc; Ex ic IIC T4 Gc |
| EMC |
IEC 61326 (GB/T 18268) |
| Housing Material |
Die-Cast Aluminum (ADC12) |
| Mounting |
Wall Mounting |
| Dimensions |
MCAFD4: (170 × 145 × 80)mm
MCAFD8: (260 × 145 × 100)mm
MCAFD12: (260 × 145 × 100)mm |
| Weight |
MCAFD4: Approx. 1.5kg
MCAFD8: Approx. 2.4kg
MCAFD12: Approx. 2.4kg |